An exception is made for non combustible walls such as solid masonry or concrete.
Furnace vent pipe clearance height above roof.
The 1992 vent sizing tables require that all type b gas vents terminate above the roof with a listed cap or listed roof assembly in accordance with the manufacturer s instructions.
Vent pipes should extend to outdoors above the building roof and should terminate vertically not less than 6 above the roof surface nor more than 24 and must be at least 12 from any vertical surface such as a nearby sidewall.
Vent caps 12 and smaller may terminate a distance above the roof if 8 feet or more away from a vertical surface as follows.
If the pipe is farther than 10 feet from the roof.
This specification makes sure steep roof slopes are cleared.
Vertical blue line along the left side of the chimney in our photo.
If the previous calculation results in the required height of 64 inches we can see that the top of the pipe will not rise above the roof peak but would still meet the requirements of the rule.
The top of the chimney should be at least 3 ft 0 92 m above the roof surface.
Also known as the type b this vent is operating on the natural air convection.
For gas fired water heater vents.
For gas vents or a type l vent this distance above the roof surface must be at least 2 ft 0 61m.
When the vent is withdrawing air from the house it expels the gas outside through the vent.
Table illustrations of the required space between a direct or side wall vent for a gas fired heating appliance and building windows doors corners gas meter air intakes sidewalks balconies.
Table of type b vent rooftop clearance requirements.
The top of a chimney pipe must extend at least 2 feet above the peak of the roof if the pipe is within 10 feet of the peak.
6 minimum clearance from single wall vent pipe or flue vent connector to any combustible material.
Gas appliance direct vent clearances distances from direct gas vent to building features sidewall vent direct vent direct exhaust systems for gas fired heaters water heaters other appliances.
Above the roof plumbing vent height.
Single wall vent pipes cannot pass through a ceiling floor firewall or wall.
Notes to the table above 1 measure on the up roof or shorter height side of the chimney 2 watch out.
This structure generally uses the furnace vent pipe through roofbecause the b venting pipe is designed in vertical manner.
Upc i 906 1 and 906 2.